| | 4 | |
| | 5 | == Apr 2 (Rita) == |
| | 6 | - power outage for parts of Kihei from approx. 4/1/13 @ 10:30PM - 4/2/13 1AM affected the MHPCC PanSTARRS IPP cluster. The IPP Panstarrs system unfortunately went down along with the UPS' about 45 minutes after the outage. I went to MHPCC 4/2 at 9Am to check it out: |
| | 7 | All but 4 servers had restarted when power was restored. |
| | 8 | - ipp046 - needed to have the BIOS reset. Once that was done the reboot went fine. |
| | 9 | - ipp048 - had rebooted automatically and was running fsck, which took some time, but eventually recovered without problems. |
| | 10 | - ippc17 - had to be power cycled a few times, and then it did reboot without problems. |
| | 11 | - ippc19 - got no response after a few power cycles. Opened the box and reset the CMOS. When trying to re-power the server, saw an FF on LED and then Eddie and I smelled something burning and quickly unplugged power. |
| | 12 | Brought the server back to the ATRC to investigate and it appears that the voltage regulator to the CPU had burned - MOBO must be replaced. |